1250 KVA DIESEL GENERATORS ON RENT
1250 kVA DG Set Rental Company
Get a Quote
Rent a 1250kVA diesel generator for temporary power needs
Modern Hiring Service offers 1250kVA diesel generators for rent to meet temporary power needs. Renting our 1250kVA diesel generators is common across many industries. Diesel generators are available for short and long-term hire. We can serve even the most remote locations thanks to our experience and pan-India network. Rent a 1250kVA Diesel Generator for the lowest possible price.
Get the best price for diesel generator rentals of 1250 kVA in India by contacting us today.
Technical Specification for 1250 kVA DG Sets for Rent
GENERATOR SET SPECIFICATION | FEATURES |
---|---|
MODEL | C1250D5P |
PRIME POWER RATING kVA/kWE | 1250 |
OUTPUT VOLTAGE AND FREQUENCY (V & HZ) | 415 V, 50HZ |
POWER FACTOR | 0.8 (LAGGING) |
NUMBER OF PHASES | 3 |
ENGINE SPECIFICATION | FEATURES |
---|---|
MAKE | MODERN HIRING SERVICE |
MODEL | KTA50 G3 |
NUMBER OF CYLINDERS | 16'VEE |
ASPIRATION | TURBO CHARGED - AFTER COOLED |
Bore(mm) * STROKE (mm) | 159*159 |
DISPLACEMENT (litre) | 50.3 |
OUTPUT - PRIME | 1470BHP (1097KWm) |
FUEL CONSUMPTION @75% LOAD WITH RADIATOR AND FAN* (litre/hr) | 190.8 |
FUEL CONSUMPTION @100% LOAD WITH RADIATOR AND FAN* | 251.8 |
TOTAL WET WEIGHT(ENGINE+RADIATOR) (kg) | 6824 |
LENGHT*WIDHT*HEIGHT(inch)(mm) | 2978*2080*1780 |
COMPRESSION RATIO | 13.9:1 |
PISTON SPEED(m/s) | 7.95 |
GOVERNOR/CLASS | ELECTRONIC/A1 |
LUBRICATING OIL SYSTEM CAPACITY | 177 litre |
COOLANT CAPACITY (ENGINE+RADIATOR)(litre) | 440 |
COMBUSTION AIR INTAKE@100% LOAD (±5%)(cfm) | 81.6 m^3/mins |
FAN AIR FLOWACROSS RADIATOR | 27357 litre/sec |
EXHAUST TEMPERATURE (°C) | 529 DEGREE C |
ALTERNATOR SPECIFICATION | FEATURES |
---|---|
MAKE | STAMPORD(CGT) |
ALTERNATOR FRAME SIZE/MODEL NUMBER | HCK6Z |
VOLTAGE REGULATION(MAX) | ±5% |
INSULATION | H CLASS |
STANDARD ENCLOSURE | IP 23 |
WINDING PITCH | 2/3 |
STATOR WINDING | DOUBLE LAYER LAP |
ROTOR | DYNAMICALLY BALANCED |
WAVEFORM DISTORTION | NO LOAD<1.8%,NON DISTORTING /BALANCED LINEAR LOAD<5% |
TELEPHONIC INTERFERENCE FACTOR | BETTER THAN 50 |
TOTAL HARMONIC FACTOR | BETTER THAN 2% |